cabecera

 
 

Optimal Voltage Sags Monitoring Considering Different Loading Profiles in Distribution Systems

T. R. Kempner, F. A. Mourinho, F. B. Bottura, M. Oleskovicz, J. C. M. Vieira, J. R. Lima Filho

2016/5/20

Abstract

This research aims to assess the influence of different distribution systems loading profiles on the optimized placement process of Power Quality (PQ) monitors. Therefore it is presented a placement methodology that considers different loading profiles in the IEEE 34 nodes test feeder. The placement methodology is a branch and bound based algorithm which includes single phase short-circuits simulations with different fault resistances at each one of all considered loading profiles. An observability index is evaluated and introduced in the optimization process in order to prioritize monitors placement at the most sensitized nodes regarding voltage sags. Results reveal that the proposed placement methodology was able to provide feasible solutions, which contain the same placement nodes for all considered loading profiles. Thus, there are significant evidences that it is possible to properly carry out the optimal placement of PQ monitors, assuming the distribution system modeled and simulated without loads.

Published in: Renewable Energy & Power Quality Journal (RE&PQJ, Nº. 14)
Pages:306-311 Date of Publication: 2016/5/20
ISSN: 2172-038X Date of Current Version:2016/05/04
REF:300-16 Issue Date: May 2016
DOI:10.24084/repqj14.300 Publisher: EA4EPQ

Authors and affiliations

T. R. Kempner(1), F. A. Mourinho(1), F. B. Bottura(1), M. Oleskovicz(1), J. C. M. Vieira(1), J. R. Lima Filho(2)
1. Department of Electrical and Computer Engineering. University of São Paulo-São Carlos School of Engineering. Laboratório de Sistemas de Energia Elétrica. Brazil
2. Research, Development and Energetic Efficiency Managment. Eletrobras Distribuição Piauí - EDPI. Brazil

Key words

Distribution systems, power quality, optimal allocation, load profile, voltage sags.

References

[1] M. F. Mcranaghan, D. R. Mueller and M. J. Samotyj, "Voltage Sags in Industrial Systems," Industry Applications, IEEE Transactions on, vol.29, no.2, pp.397- 403, Mar/Apr 1993.
[2] M. H. J. Bollen, M. R Qader and R. N. Allan, "Stochastical and statistical assessment of voltage dips," Tools and
Techniques for Dealing with Uncertainty (Digest No. 1998/200), IEEE Colloquium on, pp.5/1-5/4, 27 Jan 1998.
[3] IEEE Recommended Practice for Monitoring Electric Power Quality, IEEE Standard 1159 – 1995, Nov. 1995.
[4] M. H. J. Bollen, "Voltage sag: Effects, Mitigation and Prediction," Power Engineering Journal, vol.10, no.3,
pp.129-135, June 1996.
[5] G. Olguin, F. Vuinovich and M. H. J. Bollen, "An optimal monitoring program for obtaining Voltage sag system
indexes," Power Systems, IEEE Transactions on , vol.21, no.1, pp. 378- 384, Feb. 2006.
[6] D. C. S. Reis, P. R. C. Villela, C. A. Duque and P. F. Ribeiro, "Transmission Systems Power Quality Monitors
Allocation," Power and Energy Society General Meeting -Conversion and Delivery of Electrical Energy in the 21st
Century, 2008 IEEE , pp.1-7, 20-24, July 2008.
[7] E. Espinosa-Juárez, A. Hernandes and G. Olguin, "An Approach Based on Analytical Expressions for Optimal
Location of Voltage Sags Monitors," Power Delivery, IEEE Transactions on , vol.24, no.4, pp.2034-2042, Oct. 2009.
[8] C. F. M. Almeida and N. Kagan, "Allocation of Power Quality Monitors by Genetic Algorithms and Fuzzy Sets
Theory," Intelligent System Applications to Power Systems, 2009. ISAP '09. 15th International Conference on, pp.1,6, 8-12, Nov. 2009.
[9] F. Salim and K. M. Nor, "Voltage sags observation through optimal monitor locations," In Harmonics and Quality of Power (ICHQP), 14th International Conference on, 2010.
[10] M. Oleskovicz, H. M. G. C. Branco, R. P. M. da Silva, D.V. Coury and A. C. B. Delbem, "A Compact Genetic
Algorithm structure used for the optimum allocation of power quality monitors based on electrical circuit topology," in Harmonics and Quality of Power (ICHQP), 2012 IEEE 15th International Conference on , pp.34-39, 17-20, June 2012.
[11] T. R. Kempner, A. Q. Santos and M. Oleskovicz, "Optimized monitoring of voltage sags in distribution systems caused by balanced and unbalanced shortcircuits," in PES General Meeting | Conference & Exposition, 2014 IEEE , pp.1-5, 27-31, July 2014.
[12] IEEE PES Test Feeders, "Distribution System Analysis Subcommittee," IEEE Power Engineering Society,
Available: http://www.ewh.ieee.org/soc/pes/dsacom/testfeeders.html
[13] W. H. Kersting, Distribution System Modeling and Analysis. 2nd ed. Boca Raton, Florida USA. CRC Press
LLC. 421p., 2007.
[14] ATPDraw, “Help and about ATPDraw,” Avaliable: http://www.atpdraw.net/help.php.
[15] L. A. Wolsey, Integer Programming, John Wiley & Sons, ISBN: 9780471283669, 1998.
[16] EPRI – Electric Power Research Institute. Distribution System Power Quality Assessment: Phase II. Voltage Sag
and Interruption Analysis. Project Manager A. Sundaram, pp. 5-17, 2003.

 